Article CCN#2

 

THE CAPILLARY TUBE EXPANSION DEVICE : Part 2

As we stated in the last issue, the first danger is associated with an approximate charge. The superheat depends on the temperature of the air at the evaporator inlet.

To enable us to better understand the next problem, let's examine the arrangement below ;

Water is ejected into the open air (at atmospheric pressure) through a capillary.

If the water is at a pressure of 3 bars, an amount M1 of water is ejected in a given time (DP between the terminals of the capillary is then 3 bars).

If the water supply pressure is reduced to 1 bar (DP across the capillary is then only 1 bar), it is easy to see that the amount M2 of water being ejected in a given time becomes smaller.

So, when DP across the capillary terminals falls, the mass flow of water being injected also falls.

Naturally, the same effect is produced if R22 is used instead of water.

Therefore, the liquid mass flow through the capillary is larger if the pressure difference between HP and LP increases.

In practice, the more the HP increases, the larger the increase in the amount of refrigerant being injected into the evaporator will be.

This effect has consequences for the operation of the system.

To understand what these are, let's examine the diagram opposite.

Let's assume that with an ambient temperature of 20°C the HP is 14.3 bars (+40°C) and the LP is 4.1 bars (+1°C).

This mean that DP between the terminals of the capillary is 10.2 bars. At this point the compressor suction side temperature is 8°C, which gives us a superheat of 8 - 1 = 7°C.

Whatever the cause (fouled condenser, increase in air temperature at the condenser inlet etc.), let's now imagine that the HP increases to, say, 18.5 bar. Since the HP increases, the compressor draws in less vapour (see: Effect of pressure on mass flow, Refrepair manual page 41) and the LP also increases to, say, 4.6 bar.

DP across the capillary rises from 10.2 bar to 13.9 bar. This causes a noticeable increase in the amount of liquid injected into the evaporator. The last droplet of liquid to evaporate therefore moves closer to the compressor, and the superheat measured at the compressor inlet falls (in the example it's only 6 - 4 = 2°C).

This, then, is the second danger associated with an approximate charge. The superheat depends on the HP value.

When a capillary expansion valve is fitted to an air-conditioning unit, another problem can prevent normal operation being achieved. The problem concerns the rotation speed of the fan (A/C units are usually fitted with multi-speed motors). Remember that with this equipment, high speed is used in summer to prevent blowing air that is too cold into a room. Low speed is usually used for heating in winter for warmer air to be blown out.

Imagine that the air-conditioning unit is set to maintain an ambient temperature of 20°C. Since the apparatus is running at high speed, a large volume of air is flowing over the evaporator. Everything is operating satisfactorily, and the superheat at the end of a cycle is quite normal.

If the client now switches the equipment to low speed (often because he finds the high-speed operation too noisy) the flow of air over the evaporator decreases. Since there is less air passing over the evaporator, the liquid refrigerant evaporates more slowly and it slowly 'creeps' towards the compressor. The superheat then decreases dangerously.

There is then a good chance that the compressor will experience destructive liquid hammer.

Indeed, most of the causes of lack of evaporator capacity studied can cause dangerous liquid slugging in this type of installation, whether in air conditioning or commercial refrigeration applications. This is because there is no thermostatic expansion valve controlling the amount of liquid being injected (see: Lack of evaporator capacity - some practical aspects, Refrepair manual page 114).

 

D) When is a system fully charged?

The best way of charging a system equipped with a capillary expansion device is doubtless to charge it with the precise mass of refrigerant specified by the manufacturer.

This requires that all the refrigerant remaining in the equipment to be recovered. Then a vacuum must be pulled on the system, and the precise quantity of refrigerant indicated on the identification plate should be introduced from a charging cylinder or using a balance of adequate precision.

On site, an engineer confronted with a lack of refrigerant generally doesn't have immediate access to a charging cylinder or balance. On occasion, the identification plate is missing or illegible. If it is impossible to take the equipment to the workshop for the work to be made on site, priority must be given to repairing any leaks.

When charging is performed, refrigerant must be carefully introduced (preferably in the vapour phase), whilst simultaneously measuring the changes in the superheat at the compressor inlet. With commercial refrigeration equipment it will often be possible to visually observe frosting gradually moving along the evaporator as the air temperature falls.

Depending on the operating conditions when the refrigerant is being charged into the system, an engineer needs to remember that the superheat can fall dangerously if:

  • The ambient temperature falls (it is generally higher than normal when charging takes place).
  • The HP increases (an artificial increase in HP can be produced, for example, by partially blocking the condenser with cardboard to check if the superheat stays at an acceptable level).
  • The evaporator cooling capacity falls (this is normal in air conditioning if a filter is blocked). In commercial refrigeration, the evaporator is normally frosted.

Note that too large a refrigerant charge will result in operation with the suction side superheat being too small. Excess refrigerant can then cause destructive liquid slugging which may damage the compressor.

On the other hand, too small a charge will cause a system to operate with much too high a suction side superheat. The pot of the hermetic compressor will then be poorly cooled and the compressor motor will overheat. Then we must hope that the internal safety devices will operate properly, otherwise the motor is very likely to die an early death!

Finally, let's remember that installations equipped with a capillary expansion device have a reduced refrigerant charge because the equilibration of pressures when the compressor stops means that the evaporator could become completely full.

 

Only experience will allow an engineer to estimate the precise moment when the refrigerant charge is correct. If there is any doubt at all, it is always advisable to return later to the site to make any necessary adjustments to the charge.

 

E) Problems encountered when replacing the capillary.

Unfortunately, capillaries can sometimes become partially or completely blocked. This usually happens after a compressor burnout, or after sub-standard work has been carried out on the system.

If the capillary is blocked, there will be very little liquid in the evaporator. The cooling capacity will therefore be reduced, and the superheat will be high. This will cause an abnormal temperature rise in the hermetic compressor body.


Warning: a lack of refrigerant charge produces exactly the same symptoms. However, if there is a lack of refrigerant in the system, there will also be a shortage of refrigerant in the condenser, and the sub-cooling will be small. On the other hand, if the capillary is blocked, the refrigerant missing from the evaporator will be in the condenser, and the sub-cooling will be quite normal.

Another extremely valuable index can be used to diagnose a blocked capillary with certainty. If the compressor stops, the pressures will quickly equalise. If the capillary is blocked, this pressure equalisation will not occur. If there is a partial obstruction, then the worse the blockage, the longer this equalisation takes to occur.

Be careful not to confuse a blocked capillary with a lack of refrigerant.